61
"Stop memory" means that after the inverter is stopped, the digital set frequency is retained as the set frequency
at the last stop time, and the frequency correction by the keyboard ▲, ▼ keys or terminals UP and DOWN
remains valid.
"Stop no memory" means that after the inverter stops, the digital set frequency value returns to the value of 00-06
(keyboard given frequency), and the frequency correction performed by the keyboard ▲, ▼ keys or terminals UP
and DOWN is cleared.
00-02
Main frequency source X selection
Factory setting
1
Setting range
0
Digital setting (keyboard given frequency 00-06, UP/DOWN can be
modified)
1
AVI1
2
AVI2/ACI
3
Reserved
4
Multi-speed command
5
PID control
6
Communication setting
7
Simple PLC
8
Panel potentiometer
9
Pulse setting (MI5)
Select the input channel of the main given frequency of the inverter:
0: Digital setting
The initial value of the set frequency is 00-06 "Keyboard given frequency" value. The set frequency value of the
inverter can be changed by the ▲ and ▼ keys of the keyboard (or UP and DOWN of the multi-function input
terminal).
Tip: Please refer to parameter 00-01 for UP and DOWN.
1: AVI1
2: AVI2/ACI
3: Reserved
The frequency is determined by the analog input terminal. The control board provides 2 analog input terminals
(AVI1, AVI2/ACI).
Among them, AVI1 is 0V ~ 10V voltage type input, AVI2/ACI can be 0V ~ 10V voltage input, can also be 4mA ~
20mA current input, selected by the jumper on the control board.
The corresponding relationship between the input voltage value of AVI1, AVI2/ACI and the target frequency can
be freely selected by the user.
4: Multi-speed command
When this frequency setting mode is selected, the inverter runs in multi-speed mode. Group 04 and Group 05
"multi-stage speed control group" parameters need to be set to determine the correspondence between a given
percentage and a given frequency.
5: PID
If this parameter is selected, the inverter operation mode is process PID control. At this time, 10 groups of "PID
control groups" need to be set. The running frequency of the inverter is the frequency value after PID function. For
the meaning of PID given source, given amount and feedback source, please refer to the introduction of 10
groups of "PID function".
6: Communication setting
The frequency command is given by the host computer through communication. For details, please refer to 12
Communication protocol.
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...