109
09-47
Module temperature reached
Factory setting
75
℃
Setting range 0
℃~
100
℃
When the temperature of the inverter radiator reaches this temperature, the multi-function output terminal
(function 35) of the inverter outputs an ON signal.
09-48
Cooling fan control
Factory setting
0
Setting range
0
Fans run during operation
1
The fan keeps running
It is used to select the operation mode of the cooling fan. When it is set to 0, the fan runs in the running state. If
the temperature of the radiator is higher than 40 degrees in the stopped state, the fan runs.
When selected as 1, the fan keeps running after power on.
09-49
Wake frequency
Factory setting
0.00Hz
Setting range Sleep frequency (09-51) ~ max frequency (00-03)
09-50
Wake delay time
Factory setting
0.0s
Setting range 0.0s
~
6500.0s
09-51
Sleep frequency
Factory setting
0.00Hz
Setting range 0.00Hz
~
Wake frequency(09-49)
09-52
Sleep delay time
Factory setting
0.0s
Setting range 0.0s
~
6500.0s
This group of parameters is used to implement sleep and wake-up functions in water supply applications.
During the operation of the inverter, when the set frequency is less than or equal to the sleep frequency of 09-51,
after the delay time of 09-52, the inverter enters the sleep state and automatically stops.
If the inverter is in sleep state and the current running command is valid, when the set frequency is greater than or
equal to the wake-up frequency of 09-49, the inverter will start after a delay time of 09-50.
In general, please set the wake-up frequency to be greater than or equal to the sleep frequency. If the wake-up
frequency and sleep frequency are both set to 0.00Hz, the sleep and wake-up functions are invalid.
When the sleep function is enabled, if the frequency source uses PID, whether the PID operation in the sleep
state is affected by the parameter 10-28.At this time, it is necessary to select PID calculation when the machine is
stopped (10-28=1).
09-53
Arrival time setting for this run
Factory setting
0.0Min
Setting range 0.0Min
~
6500.0Min
When the running time of this startup reaches this time, the inverter multi-function output terminal Terminal
(function 40) outputs ON signal.
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...