Frequency arrival
detection signal
(
MO1,RELAY,DFM(M)
Output frequency Hz
FDT Level
FDT hysteresis
ON
Time
Time
=09-19x09-20
Figure 5-17 Schematic diagram of FDT level
09-21
Frequency reach detection width
Factory setting
0.0%
Setting range 0.00
~
100%(Max frequency )
When the running frequency of the inverter is within a certain range of the target frequency, the multi-function
output terminal (function 4) of the inverter outputs an ON signal.
This parameter is used to set the detection range of frequency arrival. This parameter is a percentage relative to
the maximum frequency. Figure 5-18 is a schematic diagram of frequency arrival.
Frequency arrival
detection signal
Output frequency Hz
Set frequency
Detection
amplitude
ON
Time
ON
Figure 5-18 Schematic diagram of the frequency arrival detection amplitude
09-22
Whether the jump frequency is effective during
acceleration and deceleration
Factory setting
0
Setting range
0
Invalid
1
Valid
When the setting is valid, when the operating frequency is within the range of the skip frequency, the actual
operating frequency will skip the boundary of the set skip frequency. As shown in Figure 5-19.
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...