101
09 Accessibility Parameters
09-00
Jog
running frequency
Factory setting
5.00Hz
Setting range 0.00Hz
~
Max frequency
09-01
Jog acceleration time
Factory setting
20.0s
Setting range 0.0s
~
6500.0s
09-02
Jog deceleration time
Factory setting
20.0s
Setting range 0.0s
~
6500.0s
Define the given frequency and acceleration/deceleration time of the inverter when jogging.
During jog operation, the start mode is fixed to the direct start mode (07-00=0), and the stop mode is fixed to the
deceleration stop (07-05=0).
09-03
Acceleration time 2
Factory setting
Type setting
09-04
Deceleration time 2
Factory setting
Type setting
09-05
Acceleration time 3
Factory setting
Type setting
09-06
Deceleration time 3
Factory setting
Type setting
09-07
Acceleration time 4
Factory setting
Type setting
09-08
Deceleration time 4
Factory setting
Type setting
Setting range 0. 0s
~
6500.0s
S3100E provides 4 groups of acceleration and deceleration time, respectively 00-07/00-08 and the above 3
groups of acceleration and deceleration time.
The definitions of the 4 groups of acceleration and deceleration times are exactly the same, please refer to the
relevant descriptions of 00-07 and 00-08. Through different combinations of multi-function digital input terminals
MI, you can switch to select 4 groups of acceleration and deceleration time. For specific usage, please refer to the
relevant descriptions in parameters 04-00
~
04-05.
09-09
Jump frequency 1
Factory setting
0.00Hz
Setting range 0.00Hz
~
Max frequency
09-10
Jump frequency 2
Factory setting
0.00Hz
Setting range 0.00Hz
~
Max frequency
09-11
Jump frequency amplitude
Factory setting
0.00Hz
Setting range 0.00Hz
~
Max frequency
When the set frequency is within the range of the jump frequency, the actual operating frequency will run at the
jump frequency closer to the set frequency. By setting the jump frequency, the inverter can avoid the mechanical
resonance point of the load.
The S3100E can set two jump frequency points. If both jump frequencies are set to 0, the jump frequency function
is cancelled. Please refer to Figure 5-15 for the principle of jump frequency and jump frequency amplitude.
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...