Torque adjustment proportional gain
Factory setting
300
Setting range 0
~
60000
02-16
Torque adjustment integral gain
Factory setting
500
Setting range 0
~
60000
The vector control PI adjusts the parameter. This parameter is automatically obtained after the asynchronous
motor completes self-learning, and generally does not need to be modified.
02-18
Field weakening mode of synchronous motor
Factory setting
1
Setting range
0
Not weak magnetic
1
Automatic adjustment mode
2
Calcu automatic adjustment comprehensive mode
02-19
Field weakening gain of synchronous motor
Factory setting
5
Setting range 0
~
50
02-23
Output voltage upper limit margin of synchronous motor
Factory setting
5%
Setting range 0%
~
50%
This group of parameters is used for field weakening control of the synchronous motor.
(1) 02-18=0 not weak magnetic
The synchronous motor does not perform field weakening control. At this time, the maximum value of the motor
speed can be related to the inverter bus voltage. The advantage is that there is no field weakening current and
the output current is small. The disadvantage is that the operating frequency cannot reach the set frequency.
Higher speeds need to turn on the field weakening function.
(2) 02-18=1 automatic adjustment mode
This field weakening method is simple and reliable. The higher the speed, the larger the field weakening current.
When the rated current of the motor is reached, it is not allowed to increase the speed, otherwise it will report an
overload after a long time of operation. Weak magnetic coefficient 02-19, but excessive 02-19 will cause current
instability.
(3) 02-18=2 calcu automatic adjustment comprehensive mode
The speed of weak field current adjustment of the calculation + automatic adjustment synthesis method is
relatively fast. It can be set to this mode when the automatic adjustment cannot meet the requirements. However,
this mode depends on the motor parameter values, and its stability is not as good as Mode 1.
After entering the field weakening, if the output voltage is expected to be higher, so that the field weakening
current is smaller, the output voltage saturation margin of the synchronous motor can be appropriately reduced
02-23, but too small 02-23 will make the output voltage more easily saturated and affect the control performance.
02-22
The upper limit of generating torque becomes effective
Factory setting
0
Setting range
0
Close
1
Open
When 02-22 is set to 1, the upper limit of power generation torque 02-12 and the upper limit of power generation
torque 02-11 are effective. By default, there is no distinction between power generation and electric torque, and
the upper limit is 22-07
02-24
Initial position angle detection current of synchronous
motor
Factory setting
80%
Setting range 10%
~
180%
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...