![Savch S3100E Series Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/savch/s3100e-series/s3100e-series_user-manual_1203759019.webp)
15
2.4 Basic Wiring Diagram
Wiring of AC motor drive can be divided into two parts, the main circuit and control circuit. After removing the
cover, terminals of main circuit and control circuit shall be found. Users must connect terminals as diagram
shows.
The following diagram is the standard wiring diagram of S3100E series AC motor driver. If only digital control
panel was used, only main circuit terminal wiring applicable.
Main circuit terminal
Control circuit terminal
Multifunctional reference output contactor
AC 250V below 2A
DC 30V below 2A
DC reactor
Braking resistor
The third grounding resistor of
220V series (less than 100
Ω)
Grounding resistance shall
below 10
Ω for 440V series
grounding
RS485 Serial connected
communication connector
terminal
Signal - terminal
Computer
Induction motor
Assisted power supply
Analog frequency/ current meter
Analog signal terminal common
Analog voltage
frequency reference
Analog current
frequency reference
Multi-functional open collector
output terminal
48V 50mA below
Multi-functional open collector
output terminal
24V 50mA below
Short
circuit pad
Braking resistor
AC MOTOR DRIVE
N(-)
RC
RA
RB
P1
DB
P(+)
485+
485-
S/L2
T/L3
R/L1
MCCB
U/T1
V/T2
W/T3
IM
AFM
ACM
+10V
AVI1
AVI2/ACI
ACM
MO1
DCM
1
k
Ω
~
5
k
Ω
S/L2
T/L3
R/L1
DFM
DCM
24V
PNP
SW1
NPN
D
C
+
2
4
V
MI2
MI1
MI3
MI4
MI5
DCM
J3
ACI
AVI2
Multifunctional input
option 2
Multifunctional input
option 1
Multifunctional input
option 3
Digital signal common terminal
Multifunctional input
option 5
Multifunctional input
option 4
NPN mode of factory setting
Remarks:
1. The external terminal has two AVI inputs (AVI1, AVI2), one of which is shared with ACI and can be switched to
each other.
2. Analog current frequency command ACI:It can switch 4~20mA or 0~+10V as input signal according to J3.
3. There are 5 multi-function input terminals (MI1~MI5) in the external terminal, and the configuration input can be
selected.
4. The external terminals have 2 open collector outputs (MO1, DFM).
5. The external terminal has one relay output (RA-RB-RC).
6. The power of 22kW and above can be equipped with I/O expansion card: HCA-EIO-AO/MC1, the whole
machine realizes 2 analog (voltage/current optional) s 2 relay outputs.
7. The DC reactor, braking unit and braking resistor are selected according to the requirements. When using the
DC reactor, please remove the short-circuit copper sheet between P1 / P (+) before connecting.
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...