26
(F0.09) to 0 Hz, see t
2
in Figure 6-7.
F0.14 Reserved
Reserved
6.2
Motor Parameter
(
F1
)
F1.00 Reserved
Reserved
F1.01 Motor’s poles
Range
:
2
~
14
【
4
】
F1.02 Rated power
Range
:
0.4
~
1000kW
【
depending on model
】
F1.03 Rated current
Range
:
0.1
~
999.9A
【
depending on model
】
F1.01~F1.03 is to set motor’s parameters. Be sure to input the values
according to motor’s nameplate.
F1.04 Current without
load
Range
:
0.1
~
6553A
【
depending on model
】
F1.05 Stator resistance
Range
:
0.0
~
50.00
%【
depending on model
】
F1.06 Leakage
inductance
Range
:
0.0
~
50.00
%【
depending on model
】
F1.07 Rotor resistance
Range
:
0.0
~
50.00
%【
depending on model
】
F1.08 Mutual
inductance
Range
:
0.0
~
2000.0
%【
depending on model
】
After the success of the motor parameter self learning, P1.04 ~ P1.08
parameters will be automatically updated.
After change P1.02 motor rated power, P1.04 ~ P1.08 parameter value
will be back to the factory.
F1.09 Rated slip frequency
Range
:
0.00
~
20.00Hz
【
0Hz
】
The motor rated speed can be obtained by the motor nameplate.
F1.10 Auto tuning
Range
:
0
~
2
【
0
】
0: Auto-tuning is disabled