39
This function is valid for auxiliary reference frequency (F0.03=1, 2 and
3) to clear it to zero, so that the reference frequency is determined solely
by main reference.
41: Reset PLC state
When the inverter stops in PLC mode, the memorized PLC operating
information (operating stage, operating time, operating frequency, etc.)
will be cleared.
42: Clear the counter to zero
This function is to clear the counter to zero and is used in conjunction
with function 43.
43: Input signal to trigger the counter
When the setting is 43, this terminal is used to input counting pulse
signal to the internal counter of the inverter. The max.pulse frequency is
200Hz. The present counting value can be saved at power off. See F6.11
and F6.12 for details.
44
:
Reserved
45
:
Reserved
F5.08 Terminal control mode
Range
:
0
~
3
【
0
】
This parameter defines four operating modes controlled by external
terminals.
0
:
2-wire operating mode 1
Figure 6-21 2-Wire Operation Mode 1