25
corresponds to the rated voltage of the inverter
The f
H
and f
L
are defined by F0.07 and F0.08 as upper limit and lower
limit of frequency respectively.
F0.11 Running direction
Range
:
0
、
1
【
0
】
The function is used to select motor direction of rotation when running
in keypad control mode.
0
:
Forward
1
:
Reverse
In two wire terminal control mode, you can switch motor direction of
rotation by change this parameter value.
F0.12 Acc time 1
Range
:
0.1
~
3600s
(
min
)【
6.0s
】
F0.13 Dec time 1
Range
:
0.1
~
3600s
(
min
)【
6.0s
】
Figure 6-7 Acc/Dec time definition
Acc time is the time taken for the motor to accelerate from 0 Hz to the
maximum frequency (as set in F0.09), see t
1
in Figure 6-7. Dec time is
the time taken for the motor to decelerate from maximum frequency
Output frequency
t
1
f
max
t
2
Time