13
Cat
ego
ry
Terminals
Name
Function
Specification
Dig
ital
inp
ut
X1
~
X5
Multi-func
tional
digital
inputs 1
~
5
Can be defined as
multi-functional digital
inputs,
see Section 7.6
Reference ground:
COM
Optical-isolator 2-way input
input resistance: 2k
Ω
maximum input frequency:
200Hz
Input voltage range: 9~30V
PLC
Common
terminal
Common terminal for
multi-functional inputs
P24
+24V
supply
Pro24V power
supply
Output
:
+24V,set point
accuracy
:
±10%
Max output current
:
200mA
COM
+24V
common
terminal
Isolated internally with
GND
Isolated internally with GND
Dig
ital
inp
ut
Y1
Open
collector
output 1
Programmable
terminals, defined as
multi-function digital
outputs, see Section
7.7.
Optical-isolator output:
24VDC/50mA
Po
wer
sup
ply
+10V
+
10V
power
supply
P10V power
supply
Output: +10V,
Setpoint accuracy: ±10%
Max. output current: 100mA
GND
GND of
+
10V
power
supply
reference ground of
analog signal and 10V
power supply
Isolated internally with COM
Oth
ers
TA/TB/T
C
Relay
output
TA, TB and TC can be
defined as
multi-functional digital
output signals. please
refer to Section 7.7
TA-TB
:
normally closed
;
TA-TC
:
normally open
Contact capacity
:
250Vac/2A
(
COS
φ
=1
),
250Vac/1A
(
COS
φ
=0.4
),
30 Vdc /1A