29
F2.03~F2.07 Reserved
Reserved
F2.08 Stop mode
Range
:
0
、
1
、
2
【
0
】
0
:
Decelerate to stop
When the inverter receives Stop command, it will reduce output
frequency to zero and stop within preset deceleration time.
1
:
Coast to stop
When the inverter receives Stop command, it will stop outputting
frequency and stop gradually relying on load inertia.
2
:
Decele DC braking
When the inverter receives Stop command, it will reduce output
frequency within preset Dec time. When it arrives at the frequency
threshold of DC braking, the DC braking begins. Please refer to
F2.09~F2.12.
F2.09 Frequency threshold of DC
braking
Range
:
0.00
~
60.00Hz
【
1.00Hz
】
F2.10 DC brake delay time
Range
:
0.00
~
10.00s
【
0.00s
】
F2.11 DC brake current at stop
0.0~150.0
%【
120.0
%】
F2.12 DC brake time at stop
0.1
~
60.0s
【
0.5s
】
DC brake starting frequency: in stop process, when the frequency is
reached, began to DC brake.
DC brake delay time: before the start of the DC brake, inverter blockade
pulse, after the delay time, began to dc brake, used to prevent current
overshoot of high-power motor brake starting time.
DC braking current: DC braking current relative to the percentage of the
frequency converter rated current.
F2.13 Dynamic braking
Range
:
0
,
1
【
0
】
0
:
Disabled
1
:
Enabled