FP.01 is to set the mode of write-in protection of parameters.
0: All parameters are allowed to be changed;
;
1: No parameters can be changed except the F0.04 and FP.01;
2: No parameters can be changed except FP.01.
0: disabled
1: clear fault record
Clear the contents of FL.14~FL.19.
2: restore to factory defaults
If FP.02 is set at 2, the parameters listed before FL.14 except F1.00 and
F1.09will be restored to factory defaults.
。
After the initialization, the parameter will change to 0 automatically.
6.19
Factory Default
(
FU
)
FP.02 Parameter initialization
Range
:
0
~
2
【
0
】
FP.03~FP.06 Reserved
Reserved
FU.00 User password
****