63
Auto current limiting function is used to limit the load current under the
preset current in real time to avoid trip due to over-current. This function
is especially useful for the applications of larger load inertia or sharp
change of load.
FL.07 defines the threshold for current limiting. Its setting is a
percentage of inverter’s rated current.
The action mode of auto current limiting function is decided by FL.09.
FL.09
=
0: When running in constant speed, auto current limit is invalid
FL.09
=
1: When running in constant speed, auto current limit is valid
FL.09
=
2: Auto current limit is valid all the time (mode 1)
FL.09
=
3: Reserved
FL.09
=
4: Reserved
FL.09
=
5: Auto current limit is valid all the time (mode 2)
Because the output frequency might change during current limiting, the
function should be used for applications that require constant speed and
stable frequency output.
FL.04~ FL.06 Reserved
Reserved
FL.07 Auto current limiting threshold
Range
:
20~200%
【
160%
】
FL.08 Reserved
Reserved
FL.09 Action mode of auto current limiting
Range
:
0
~
5
【
5
】
FL.10~ FL.13 Reserved
Reserved
FL.14 Fault type of the first two times
Range
:
0
~
29
【
0
】
FL.15 Fault type of the previous time
Range
:
0
~
29
【
0
】
FL.16 Fault type of the last time
Range
:
0
~
29
【
0
】
FL.17 Bus voltage at the last fault
Range
:
0
~
999V
【
0V
】
FL.18 Output current at the last fault
Range
:
0
~
6553A
【
0.0A
】
FL.19 Freq. at the last fault
Range
:
0.00
~
650.00Hz
【
0.00Hz
】
FL.20 Heatsink 1 temperature at the last fault Range
:
0.0
~
120.0
℃【
0
℃】
FL.21Reserved
Reserved