11
4.2.2 Power Terminals
1
.
Definitions of power terminals
Table 4-2Definitions of power terminals
Terminal name
Description
R
、
S
、
T
/L
、
N
3-phase AC input /
1-phase AC input
(+)
、
PB
External braking resistor
(+)
、
(-)
DC positive, negative bus input
U
、
V
、
W
3-phase AC outputs
Protective earth
4.2.3 Control Circuit Wiring
Control Terminals and Jumpers
The terminal row and jumpers on control panel is CN4, CN5, CN6
Control terminals functions are listed in Table 3-4
,
Jumper’s functions
in 3-5. Be sure to set the jumper and wire the terminals properly. It is
recommended to use cable of section area bigger than 1mm
2
.
Table 4-3 Function of control terminals
Mark
Function
CN8- CN10
Analog I/O, digital I/O, relay outputs
Mark
Function&Setting
Default
CN4
CCI current/voltage input selection
I
:
0
~
20mA current signal
V
:
0
~
10V voltage signal
0
~
+10V
CN5
485 terminal resistor selection
:
ON: 120
Ω
terminal resistor
OFF: No terminal resistor.
No terminal
resistor
CN6
AO current/voltage input selection
0/4~20mA: AO current signal
0/2~10V: AO voltage signal
0
~