4.6.2
Motor Connection
The ASA 4.0 Advanced can be connected to the motor in-line or inside delta (also called three-wire and six-wire connection). When
connecting in inside delta, enter the motor full load current (FLC) for parameter 1B. The ASA 4.0 Advanced will automatically detect
whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
NOTE
If the starter is not correctly detecting the motor connection, use parameter 20F
Motor Connection
.
In-line installation
34
33
K1
K1
F1
6/T3
2/T1
5/L3
3/L2
1/L1
4/T2
M
3
K1
Main contactor (strongly recommended)
F1
Fuses or circuit breaker (optional)
33, 34
Main contactor output
Inside delta installation
M
3
U1(1)
U2(4)
V1(2)
V2(5)
W1(3)
W2(6)
K1
F1
34
33
K1
6/T3
2/T1
5/L3
3/L2
1/L1
4/T2
K1
Main contactor
F1
Fuses or circuit breaker (optional)
33, 34
Main contactor output