4
Installation
WARNING
Do not apply mains voltage to the starter until all wiring is complete.
WARNING
Always apply control voltage before (or with) mains voltage.
4.1
Command Source
The ASA 4.0 Advanced can be started and stopped via the digital inputs, remote keypad, communication network, smart card or
scheduled auto-start/stop. The command source can be set via the Setup Tools, or using parameter 1A
Command Source
.
4.2
Setup Procedure Overview
1.
Mount the soft starter (refer to
Physical Installation
on page 9 for details).
2.
Connect control wiring (refer to
Input Terminals
on page 17 for details).
3.
Apply control voltage to the starter.
4.
Configure your application:
1.
Press
MENU
to open the Menu.
2.
Press to open the Quick Setup menu.
3.
Scroll through the list to find your application, then press to begin the configuration process (refer to
Quick Setup
on page
23 for details).
5.
If your application is not listed in Quick Setup:
1.
Press to return to the Menu.
2.
Use to scroll to Main Menu and press .
3.
Scroll to Motor Details and press , then press again to edit parameter 1B
Motor Full Load Current
.
4.
Set parameter 1B to match the motor's full load current (FLC).
5.
Press to save the setting.
6.
Close the Menu by pressing repeatedly.
7.
(Optional) Use the built-in simulation tools to check that the control wiring is connected correctly (refer to
Run simulation
on page
8.
Power off the soft starter.
9.
Connect the motor cables to starter output terminals 2/T1, 4/T2, 6/T3.
10.
Connect mains supply cables to starter input terminals 1/L1, 3/L2, 5/L3 (refer to
Power Terminations
on page 20).
The soft starter is now ready to control the motor.
16/78
ASA 4.0 Advanced
Содержание ASA 4.0 Advanced