33D –
Stop Pressure Level
Range:
0 – 5000
Default:
10
Description:
Sets the pressure level to trigger the soft starter to stop the motor.
33E –
Stop Response Delay
Range:
00:00:10 – 30:00:00 mm:ss:ms
Default:
00:00:500 ms
Description:
Sets a delay between the pressure passing the pressure control stop level, and the soft starter stopping the motor.
9.22
34 Depth Protection
NOTE
The parameters in this group are only active if a smart card is installed.
Depth protection uses terminals B13, B14 or C13, C14 on the smart card.
34A –
Depth Trip Level
Range:
0 – 1000
Default:
5
Description:
Sets the trip point for depth protection.
34B –
Depth Reset Level
Range:
0 – 1000
Default:
10
Description:
Sets the level for the soft starter to auto-reset a depth trip.
34C –
Depth Start Delay
Range:
00:00:10 – 30:00:00 mm:ss:ms
Default:
00:00:500 milliseconds
Description:
Sets a delay before a depth protection trip can occur. The delay is counted from the time a start signal is received.
The depth input is ignored until the start delay has elapsed.
34D –
Depth Response Delay
Range:
00:00:10 – 30:00:00 mm:ss:ms
Default:
00:00:500 ms
Description:
Sets a delay between the depth passing the depth protection trip level, and the soft starter tripping.
9.23
35 Thermal Protection
NOTE
The parameters in this group are only active if a smart card is installed.
35A –
Temperature Sensor Type
Options:
None (default)
PT100
Description:
Selects which type of sensor is associated with the temperature sensor input on the smart card.
35B –
Temperature Trip Level
Range:
0° – 240°
Default:
40°
Description:
Sets the trip point for temperature protection. Use parameter 10B
Temperature Scale
to configure the temperature
scale.
9.24
36 Pump Trip Action
36A –
Pressure Sensor
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response if it detects a fault with the pressure sensor.
ASA 4.0 Advanced
69/78