5Q –
Starts per Hour
Range:
0 - 10
Default:
0
Description:
Sets the maximum number of starts the ASA 4.0 Advanced will attempt in a 60 minute period. A setting of 0
disables this protection.
5R –
Phase Sequence
Options:
Any Sequence (default)
Positive Only
Negative Only
Description:
Selects which phase sequences the soft starter will allow at a start. During its pre-start checks, the starter
examines the sequence of the phases at its input terminals and trips if the actual sequence does not match the
selected option.
CAUTION
When using DC brake, the mains supply must be connected to the soft starter (input terminals L1, L2, L3) in positive phase
sequence and parameter 5R
Phase Sequence
must be set to Positive Only.
9.10
6 Protection Action
6A –
Auto-Reset Count
Range:
0 – 5
Default:
0
Description:
Sets how many times the soft starter will auto-reset, if it continues to trip.
The reset counter increases by one each time the soft starter auto-resets, and resets after a successful start.
Setting 6A to zero disables auto-reset.
6B –
Auto-Reset Delay
Range:
0:05 - 15:00 (minutes:seconds)
Default:
5 seconds
Description:
Sets a delay before the soft starter will auto-reset a trip.
6C –
Current Imbalance
Options:
Soft Trip and Log (default)
The soft starter will stop the motor as selected in parameter 2I or 3K
Stop Mode
,
then enter trip state. The trip must be reset before the ASA 4.0 Advanced can
restart.
Soft Trip and Reset
The soft starter will stop the motor as selected in parameter 2I or 3K
Stop Mode
,
then enter trip state. The trip will reset after the auto-reset delay.
Trip Starter
The soft starter will remove power and the motor will coast to stop. The trip
must be reset before the ASA 4.0 Advanced can restart.
Trip and Reset
The soft starter will remove power and the motor will coast to stop. The trip will
reset after the auto-reset delay.
Warn and Log
The protection will be written to the event log and the display will show a
warning message, but the soft starter will continue to operate.
Log Only
The protection will be written to the event log but the soft starter will continue to
operate.
Description:
Selects the soft starter's response to each protection. All protection events are written to the event log.
6D –
Undercurrent
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6E –
Overcurrent
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
ASA 4.0 Advanced
55/78