7K –
Input B Name
Options:
Input B Trip (default)
Controller
Low Pressure
PLC
High Pressure
Vibration Alarm
Pump Fault
Field Trip
Low Level
Interlock Trip
High Level
Motor Temperature
No Flow
Motor Protection
Starter Disable
Feeder Protection
Custom Message
Description:
Selects a message for the keypad to display when Input B is active.
9.12
8 Relay Outputs
8A –
Relay A Function
Options:
Off
Relay A is not used.
Ready
The relay is closed when the starter is in Ready state.
Run (default)
The Run output closes when the soft start is complete (when the starting current
falls below 120% of the programmed motor full load current) and remains closed
until the beginning of a stop (either soft stop or coast to stop).
Warning
The relay closes when the starter issues a warning (refer to
6 Protection Action
Trip
The relay closes when the starter trips (refer to
6 Protection Action
on page 55).
Low Current Flag
The relay closes when the low current flag activates while the motor is running
(refer to parameter 8G
Low Current Flag
).
High Current Flag
The relay closes when the high current flag activates while the motor is running
(refer to parameter 8H
High Current Flag
).
Motor Temperature Flag
The relay closes when the motor temperature flag activates (refer to parameter
8I
Motor Temperature Flag
).
Soft Brake Relay
The relay closes when the soft starter receives a stop signal, and remains
closed until the end of soft brake.
Reversing Contactor
The relay will control an external contactor, for reverse operation. Refer to
Reverse Direction Operation
on page 39 for details.
Description:
Selects the function of Relay A. Relay A is a changeover relay.
8B –
Relay A On Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for changing the state of Relay A.
8C –
Relay A Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for changing the state of Relay A.
8D –
Relay B Function
Options:
Off
Low Current Flag
Ready
High Current Flag
Run (default)
Motor Temperature Flag
Warning
Soft Brake Relay
Trip
Reversing Contactor
Description:
Selects the function of Relay B (normally open). Refer to parameter 8A
Relay A Function
for details.
8E –
Relay B On Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for closing Relay B.
8F –
Relay B Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for re-opening Relay B.
ASA 4.0 Advanced
59/78