1C –
Motor kW
Range:
0 - 9999 kW
Default:
0
Description:
Sets the running power of the connected motor, in kilowatts. This setting is the basis for power reporting and
protection.
NOTE
The motor nameplate may state different power ratings for different supply voltages or power connections. Ensure that the
motor kW setting is accurate for the installation.
1D –
Locked Rotor Time
Range:
0:01 - 2:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the maximum length of time the motor can sustain locked rotor current from cold before reaching its
maximum temperature. Set according to the motor datasheet.
1E –
Locked Rotor Current
Range:
400% - 1200% FLC
Default:
600%
Description:
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the
motor datasheet.
1F –
Motor Service Factor
Range:
100% - 130%
Default:
105%
Description:
Sets the motor service factor used by the thermal model. If the motor runs at full load current, it will reach 100%.
Set according to the motor datasheet.
NOTE
Parameters 1D, 1E and 1F determine the trip current for motor overload protection. The default settings of parameters
1D, 1E and 1F provide Motor Overload Protection: Class 10, Trip Current 105% of FLA (full load amperage) or
equivalent.
9.6
2 Motor Start/Stop
2A –
Start Mode
Options:
Constant Current (default)
Adaptive Control
Description:
Selects the soft start mode.
NOTE
The ASA 4.0 Advanced will apply the current limit on all soft starts, including adaptive control. If the current limit is too low or
the start ramp time (parameter 2B) is too short, the motor may not start successfully.
2B –
Start Ramp Time
Range:
0:01 - 3:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the total start time for an Adaptive Control start or the ramp time for current ramp starting (from the initial
current to the current limit).
2C –
Initial Current
Range:
100% - 600% FLC
Default:
200%
Description:
Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so that
the motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
2D –
Current Limit
Range:
100% - 600% FLC
Default:
350%
Description:
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load current.
ASA 4.0 Advanced
47/78