30J –
Pulses per Minute at Max Flow
Range:
0 – 20000
Default:
0
Description:
Calibrates the soft starter to the maximum flow volume of the flow sensor.
30K –
Units per Pulse
Range:
0 – 1000
Default:
0
Description:
Set to match how many units the flow sensor will measure for each pulse.
30L –
Depth Sensor Type
Options:
None (default)
Switch
Analog
Description:
Selects which type of sensor is associated with the depth sensor input on the smart card.
30M –
Depth Units
Options:
metres (default)
feet
Description:
Selects which units the sensor will use to report the measured depth.
30N –
Depth at 4 mA
Range:
0 – 1000
Default:
0
Description:
Calibrates the soft starter to the 4 mA (0%) level of the depth sensor input.
30O –
Depth at 20 mA
Range:
0 – 1000
Default:
0
Description:
Calibrates the soft starter to the 20 mA (100%) level of the depth sensor input.
9.19
31 Flow Protection
NOTE
The parameters in this group are only active if a smart card is installed.
Flow protection uses terminals B33, B34 or C23, C24 on the smart card.
31A –
High Flow Trip Level
Range:
0 – 5000
Default:
10
Description:
Sets the trip point for high flow protection.
31B –
Low Flow Trip Level
Range:
1 – 5000
Default:
5
Description:
Sets the trip point for low flow protection.
31C –
Flow Start Delay
Range:
00:00:50 - 30:00:00 mm:ss:ms
Default:
00:00:500 ms
Description:
Sets a delay before a flow protection trip can occur. The delay is counted from the time a start signal is received.
The flow level is ignored until the start delay has elapsed.
31D –
Flow Response Delay
Range:
00:00:10 - 30:00:00 mm:ss:ms
Default:
00:00:500 ms
Description:
Sets a delay between the flow passing the high or low flow trip levels, and the soft starter tripping.
ASA 4.0 Advanced
67/78