![Santerno ASA 4.0 Advanced Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/santerno/asa-4-0-advanced/asa-4-0-advanced_user-manual_810292044.webp)
Parameter Group
Default Setting
6
Protection Actions
6A
Auto-Reset Count
0
6B
Auto-Reset Delay
00:05 (mm:ss)
6C
Current Imbalance
Soft Trip and Log
6D
Undercurrent
Soft Trip and Log
6E
Overcurrent
Soft Trip and Log
6F
Undervoltage
Soft Trip and Log
6G
Overvoltage
Soft Trip and Log
6H
Underpower
Log Only
6I
Overpower
Log Only
6J
Excess Start Time
Soft Trip and Log
6K
Input A Trip
Soft Trip and Log
6L
Input B Trip
Soft Trip and Log
6M
Network Communications
Soft Trip and Log
6N
Remote Keypad Fault
Soft Trip and Log
6O
Frequency
Soft Trip and Log
6P
Phase Sequence
Soft Trip and Log
6Q
Motor Overtemperature
Soft Trip and Log
6R
Motor Thermistor Circuit
Soft Trip and Log
6S
Shorted SCR Action
3-Phase Control Only
6T
Battery/Clock
Soft Trip and Log
7
Inputs
7A
Input A Function
Input Trip (N/O)
7B
Input A Trip
Operating Only
7C
Input A Trip Delay
00:00 (mm:ss)
7D
Input A Initial Delay
00:00 (mm:ss)
7E
Input B Function
Input Trip (N/O)
7F
Input B Trip
Operating Only
7G
Input B Trip Delay
00:00 (mm:ss)
7H
Input B Initial Delay
00:00 (mm:ss)
7I
Reset/Enable Logic
Normally Closed (N/C)
7J
Input A Name
Input A Trip
7K
Input B Name
Input B Trip
8
Relay Outputs
8A
Relay A Function
Run
8B
Relay A On Delay
00:00 (mm:ss)
8C
Relay A Off Delay
00:00 (mm:ss)
8D
Relay B Function
Run
8E
Relay B On Delay
00:00 (mm:ss)
8F
Relay B Off Delay
00:00 (mm:ss)
8G
Low Current Flag
50%
8H
High Current Flag
100%
8I
Motor Temperature Flag
80%
8J
Main Contactor Time
400 ms
9
Analog Output
9A
Analog Output A
Current (% FLC)
9B
Analog A Scale
4-20 mA
9C
Analog A Maximum Adjustment
100%
9D
Analog A Minimum Adjustment
000%
10
Display
10A
Language
English
10B
Temperature Scale
Celsius
10C
Graph Timebase
30 seconds
10D
Graph Maximum Adjustment
400%
10E
Graph Minimum Adjustment
0%
10F
Current Calibration
100%
10G
Adjustment Lock
Read & Write
10H
User Parameter 1
Current
10I
User Parameter 2
Motor Voltage
10J
User Parameter 3
Mains Frequency
10K
User Parameter 4
Motor pf
44/78