10.2
Smart Card - Level Controlled Pump Activation
The ASA 4.0 Advanced smart card can be used to control start/stop activation of the starter, based on information from external inputs.
In this example, the ASA 4.0 Advanced controls a pump which fills a tank, with maximum and minimum water levels. A pressure sensor
is used to monitor the level of water in the tank and trigger the pump to fill the tank when water drops below the minimum level, and shut
off the pump when the maximum water level is reached.
A three-way selector switch allows the user to override sensor-based control, and manually start or stop the motor.
10
11
12
A3
A1
A2
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
13
14
34
33
K1
K1
F1
D
IGI
TA
L I
NP
UT
S
4/
20m
A I
NP
UT
S
R
TD
C24
C33
C34
C43
C13
C14
C23
C44
B14
B13
B23
B24
B33
B34
R2
R1
R3
1
A
B
C
A
B
C
2
3
4
17885.B
7
8
5
6
1
Digital inputs
K1
Main contactor
A
Manual start
10, 11
Reset input
B
Manual stop
11, 12
Start/stop input
C
Automatic operation (level-controlled)
13, 14
Programmable input A
(set = Command Override: Digital)
2
Control voltage
33, 34
Main contactor output
3
Three-phase supply
B33, B34
Flow protection
4
Smart card
B23, B24
Pressure or depth based control
5
Maximum water level
6
Flow sensor
7
Pressure sensor
8
Minimum water level
Parameter settings:
•
Parameter 1A
Command Source
: select 'Smart Card'.
•
Parameter 7A
Input A Function
: select 'Command Override: Digital'.
•
Parameters 30A~30O Pump Input Configuration: Set as required.
•
Parameters 31A~31D Flow Protection: Set as required.
•
Parameters 33A~33E Pressure Control: Set as required.
72/78
ASA 4.0 Advanced
Содержание ASA 4.0 Advanced