6O –
Frequency
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6P –
Phase Sequence
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6Q –
Motor Overtemperature
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6R –
Motor Thermistor Circuit
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6S –
Shorted SCR Action
Options:
3-Phase Control Only (default)
PowerThrough
Description:
Selects whether the soft starter will allow PowerThrough operation, if the soft starter is damaged on one phase.
The soft starter will use two-phase control, allowing the motor to continue operating in critical applications. Refer to
PowerThrough
on page 33 for further information.
6T –
Battery/Clock
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
9.11
7 Inputs
7A –
Input A Function
Options:
Command Override: Network
Overrides the setting of 1A and sets the command source to the
communications network.
Command Override: Digital
Overrides the setting of 1A and sets the command source to the digital inputs.
Command Override: Keypad
Overrides the setting of 1A and sets the command source to the remote keypad.
Input Trip (N/O) (default)
A closed circuit across 13, 14 trips the soft starter.
Input Trip (N/C)
An open circuit across 13, 14 trips the soft starter.
Emergency Mode
A closed circuit across 13, 14 activates emergency mode. When the ASA 4.0
Advanced receives a start command, it will continue to run until a stop command
is received, ignoring all trips and warnings.
Jog Forward
Activates jog operation in a forward direction.
Jog Reverse
Activates jog operation in reverse direction.
Zero Speed Sensor
An open circuit across 13, 14 indicates to the soft starter that the motor has
reached a standstill. The soft starter requires a normally open zero speed
sensor.
Motor Set Select
A closed circuit across 13, 14 instructs the starter to use the secondary motor
configuration for the next start/stop cycle.
Reverse Direction
A closed circuit across 13, 14 instructs the starter to reverse the phase
sequence for the next start.
Pump Clean
Activates the pump clean function.
Description:
Selects the function of Input A.
ASA 4.0 Advanced
57/78