2E –
Adaptive Start Profile
Options:
Early Acceleration
Constant Acceleration (default)
Late Acceleration
Description:
Selects which profile the ASA 4.0 Advanced will use for an Adaptive Control soft start.
NOTE
The ASA 4.0 Advanced will apply the current limit on all soft starts, including adaptive control. If the current limit is too low or
the start ramp time (parameter 2B) is too short, the motor may not start successfully.
2F –
Kickstart Time
Range:
0 – 2000 milliseconds
Default:
0000 milliseconds
Description:
Sets the kickstart duration. A setting of 0 disables kickstart.
2G –
Kickstart Level
Range:
100% - 700% FLC
Default:
500%
Description:
Sets the level of the kickstart current.
CAUTION
Kickstart subjects the mechanical equipment to increased torque levels. Ensure the motor, load and couplings can handle
the additional torque before using this feature.
2H –
Jog Torque
The ASA 4.0 Advanced can jog the motor at a reduced speed, which allows precise positioning of belts and flywheels. Jog can be used
for either forward or reverse operation.
Range:
20% - 100%
Default:
50%
Description:
Sets the current limit for jog operation.
2I –
Stop Mode
Options:
Coast To Stop
TVR Soft Stop (default)
Adaptive Control
DC Brake
Soft Brake
Description:
Selects the stop mode.
2J –
Stop Time
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets the time for soft stopping the motor using timed voltage ramp or Adaptive Control.
If a main contactor is installed, the contactor must remain closed until the end of the stop time. Use the main
contactor output (33, 34) to control the main contactor.
2K –
Adaptive Stop Profile
Options:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Description:
Selects which profile the ASA 4.0 Advanced will use for an Adaptive Control soft stop.
2L –
Adaptive Control Gain
Range:
1% - 200%
Default:
75%
Description:
Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control.
2M –
Multi Pump
Options:
Single Pump (default)
Manifold Pump
Description:
Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a common outlet
manifold.
48/78