4.4.2
Analog Output
The ASA 4.0 Advanced has an analog output, which can be connected to associated equipment to monitor motor performance.
The operation of the analog output is controlled by parameters 9A~9D.
4.4.3
Main Contactor Output
The main contactor output (33, 34) closes as soon as the soft starter receives a start command and remains closed while the soft starter
is controlling the motor (until the motor starts a coast to stop, or until the end of a soft stop). The main contactor output will also open if
the soft starter trips.
CAUTION
Some electronic contactor coils are not suitable for direct switching with PCB mount relays. Consult the contactor
manufacturer/supplier to confirm suitability.
4.4.4
Programmable Outputs
The programmable outputs (41, 42, 44 and 53, 54) can report the status of the starter, or can be used to control associated equipment.
The operation of the programmable outputs is controlled by parameters 8A~8F.
4.5
Control Voltage
4.5.1
Control Voltage Terminals
A3 A1 A2
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
B4 B5 10 11 12 13 14 15 21 22
33 34 41 42 44 53 54
A3 A1 A2
Connect the control supply according to the supply voltage being used.
•
ASA4.0-A xxxxB/x/
12
(110~120 VAC): A1, A2
•
ASA4.0-A xxxxB/x/
12
(220~240 VAC): A2, A3
•
ASA4.0-A xxxxB/x/
14
(24 VAC/VDC): A1, A2