5E –
Overcurrent
Range:
80% - 600%
Default:
400%
Description:
Sets the trip point for overcurrent protection, as a percentage of motor full load current.
5F –
Overcurrent Delay
Range:
0:00 - 1:00 (minutes:seconds)
Default:
0 second
Description:
Slows the ASA 4.0 Advanced's response to overcurrent, avoiding trips due to momentary overcurrent events.
5G –
Undervoltage
Range:
100 - 1000 V
Default:
350
Description:
Sets the trip point for undervoltage protection. Set as required.
NOTE
Voltage protections will not operate correctly until the starter is in Run mode.
5H –
Undervoltage Delay
Range:
0:00 - 1:00 (minutes:seconds)
Default:
1 second
Description:
Slows the ASA 4.0 Advanced's response to undervoltage, avoiding trips due to momentary fluctuations.
5I –
Overvoltage
Range:
100 - 1000 V
Default:
500
Description:
Sets the trip point for overvoltage protection. Set as required.
5J –
Overvoltage Delay
Range:
0:00 - 1:00 (minutes:seconds)
Default:
1 second
Description:
Slows the ASA 4.0 Advanced's response to overvoltage, avoiding trips due to momentary fluctuations.
5K –
Underpower
Range:
10% -120%
Default:
10%
Description:
Sets the trip point for underpower protection. Set as required.
5L –
Underpower Delay
Range:
0:01 - 1:00 (minutes:seconds)
Default:
1 second
Description:
Slows the ASA 4.0 Advanced's response to underpower, avoiding trips due to momentary fluctuations.
5M –
Overpower
Range:
80% -200%
Default:
150%
Description:
Sets the trip point for overpower protection. Set as required.
5N –
Overpower Delay
Range:
0:01 - 1:00 (minutes:seconds)
Default:
1 second
Description:
Slows the ASA 4.0 Advanced's response to overpower, avoiding trips due to momentary fluctuations.
5O –
Excess Start Time
Range:
0:00 - 4:00 (minutes:seconds)
Default:
20 seconds
Description:
Excess start time is the maximum time the ASA 4.0 Advanced will attempt to start the motor. If the motor does
not transition to Run mode within the programmed limit, the starter will trip. Set for a period slightly longer than
required for a normal healthy start. A setting of 0 disables excess start time protection.
5P –
Restart Delay
Range:
00:01 - 60:00 (minutes:seconds)
Default:
10 seconds
Description:
The ASA 4.0 Advanced can be configured to force a delay between the end of a stop and the beginning of the
next start. During the restart delay period, the display shows the time remaining before another start can be
attempted.