22
Auto reset sequence
In this mode, the contacts returning to normal on an acknowledged alarm causes that alarm
to reset.
If the alarm contact returns to normal prior to being acknowledged, the alarm will reset
immediately on Acknowledge.
Ringback sequence
This mode is used to indicate to operators that the alarm contact has returned back to its
normal state hence avoiding having to continually press the reset pushbutton, to see if the
plant contacts have returned to their non alarm state.
TO CHANGE FROM ONE SEQUENCE TO ANOTHER SEE THE DIL SWITCH SETTINGS
DETAILS IN THE SECTION 14: SYSTEM CONFIGURATION AND PROGRAMMING