Sequence features
Acknowledge, first-up reset and lamp test pushbuttons required
Alarm audible device
Lock-in of momentary first alarm until acknowledged.
First-up flashing different from subsequent flashing.
First-up reset pushbutton to change the first-up visual indication to be the same as
subsequent visual indication.
Automatic reset of acknowledged alarms when process conditions return to normal