SECTION 16 TROUBLE SHOOTING
For these checks the annunciator fascia and terminal cover can be removed whilst the unit is
powered.
There is no displays visible on either LCD or LED - Check
1. The power to the IS Isolator is switched on
2. The output from the IS Isolator is correct
3. The unit has not been connected directly to 24VDC
4. Inspect the Sequence Card for signs of burnt components
Displays do not operate when Test pushbutton pressed - Check
1. Voltage between Commons Card terminal 1 & 2
2. IS Isolator fuse not blown?
3. Power supply correctly wired
4. Sequence Card correctly installed
5. No earth fault on remote pushbutton controls (when fitted)
6. Field wiring is correct
All alarm channels function incorrectly - Check
1. Sequence Card correctly installed
2. Field contact wiring is correct
3. Alarm sequence is set correctly on Alarm Card DIL switches 10, 11 and 12
4. No earth fault on remote pushbutton controls (when fitted)
5.
Check functioning of Sequence Card by replacement
One channel functions incorrectly - Check
1. Alarm Card correctly installed
2. Alarm sequence is set correctly on Alarm Card DIL switches 10, 11 & 12
3. No earth fault on field contact and wiring
4. Connection is neither open nor short circuited
5. Wiring is terminated correctly
6. Check functioning of Alarm Card by replacement
The DIL Switch programming does not function - Check
1. The DIL switches have been set correctly
2. The unit has been powered down to read the new DIL switch settings
3. Is the fault related to all cards or just one
4. If just one card, check fault by card replacement
The audible is not working correctly - Check
1. If a horn is being used is it connected to the Horn connections on the Sequence Card
(Terminals 3 and 4)
2. If an external sounder is used (e.g. DB-5) is this driven via a DA-149 Relay from the
EXT SOUND Output on the Sequence Card (Terminals 11 and 12)