LN1000 IS Annunciator
11
SECTION 4 TECHNICAL SPECIFICATION
General
Location
Zone 0, IIB or IIC T4 Hazardous Area
Power Requirements
Supply voltage
20-35VDC into the IS interface
Supply current
110mA max into IS interface
Terminals
Rising clamp type terminals.
Maximum cable size 2.5mm²
Emc Compliance
RF Immunity
To IEC 801-3 level 3. 10V/m 26-1000MHz
Fast Transient Burst
To IEC 801-4 level 3
Surge withstand transient
To IEC 801-5. 1.2/50ms
Common mode: 2kV; Series mode: 4kV
Emissions
To EN50081-1 : 1992
Environment
Operating temperature
-20 to +60°C
Storage temperature
-20 to +80°C
Humidity
0-95%
RH,
non-condensing
Environmental Protection
Door to case
IP65
Case to panel
IP65
Rear of enclosure
IP20
Construction
Case
Stainless
Steel
Front fascia
High impact resistant polyurethane
Membrane
Polyester
Panel
Cut
Out
LN1000-12 (8 or 12Way)
121 x 270mm ±0.5mm (H x W)
LN1000-32 (32Way)
249 x 335mm ±0.5mm (H x W)
LN1000
Corner Radii R3 max.
Weight
LN1000-12-P
3.8kg plus 120g per Alarm Card
LN1000-32-P
8.0kg plus 120g per Alarm Card
LN1000-12-W
20.0kg plus 120g per Alarm Card
LN1000-32-W
44.0kg plus 120g per Alarm Card
}
to BS EN 60529 : 1992