LN1000 IS Annunciator
49
Alarm contact repeat outputs
If it is required that the alarm contacts are repeated into the safe area, this must be done by
isolating the signals via a DAA149 IS relay. The repeat relays are driven by the RTA output
which is set to repeat the alarm contact information. See Section 14 on System Configuration
Repeat alarm contacts to the safe area (Figure 13.5)
12
11
10
9
8
7
6
5
4
3
2
1
LN1000/AC
ALARM CARD
HAZARDOUS AREA
SAFE AREA
IS RELAY
2
DAA
149
N/O CONTACTS
1
4
3
CLOSE ON ALARM
IS RELAY
2
DAA
149
N/O CONTACTS
1
4
3
CLOSE ON ALARM
NORMALLY CLOSED
ALARM CONTACT
CHANNEL 1
NORMALLY CLOSED
ALARM CONTACT
CHANNEL 2
-
+
-
+