LN1000 IS Annunciator
51
B1 Output
The B1 output can be configured to operate in a number of different ways.
Firstly this output can be configured using DIL Switch 1 to follow the alarm sequence or the
field contacts. When set to follows the alarm sequence this output is active when any
channel is in the alarm state. The output only goes off when all alarm contacts have returned
to the normal state and the annunciator reset.
The second mode available is where the B1 output is active whenever one of the field
contacts in the "Field Contact Group" is in the abnormal condition. Channels are selected to
be in the "Field Contact Group" by DIL switches on the Alarm Card. (See next section)
Audible Re-sound
In critical alarm situations it is often important to continue to remind an operator that the
situation has not yet been dealt with. In normal situations the audible is silenced permanently
by pressing the SILENCE pushbuttons and the audible does not re-sound.
On the LN1000 it is possible to program this audible to re-sound until the alarm channel has
returned to normal.
The delay between each time the audible re-sounds is selectable, as shown in the table
below.
Audible re-sound table
SWITCH TIME
IN
MINUTES
2 3 4
UP UP UP
INFINITE
UP UP
DOWN
0.25
UP DOWN UP
0.5
UP DOWN
DOWN
1
DOWN UP
UP
2
DOWN UP DOWN
4
DOWN DOWN
UP
8
DOWN DOWN DOWN
15
Integral Pushbutton Links
The Pushbutton Card is attached to the rear of the fascia, on the rear of this card are jumper
links used to enable/disable the internal pushbuttons. See Figure 14.2
LK1 INTERNAL
SILENCE
PUSH-BUTTON
ENABLED
DISABLED
LK2 INTERNAL
ACKNOWLEDGE
PUSHBUTTON
ENABLED DISABLED
LK3 INTERNAL
RESET
PUSHBUTTON
ENABLED
DISABLED
LK4 INTERNAL
TEST
PUSHBUTTON
ENABLED
DISABLED