Application
9-49
CSD7 Servo Drive (EtherCAT)
•
dis-32 ; Load Factor of Maximum Torque
RSWare Monitoring
Select a channel that you want to use among four channels from RSWare: Drive -
Oscilloscope, and select again the following input signal.
•
Current Load Factor ; Average Torque Load Factor
•
Current Peak Load Factor ; Maximum Torque Load Factor
Average Torque Load Factor Trigger 1 & 2 Signal
The Average Torque Load Factor Trigger 1 and 2 signal, which are digital, are ON when
average torque load factor is more than the user's set value.
The user’s set values are set in 0x2418 (Ft-4.24), 0x2419 (Ft-4.25).
•
0x2418 (Ft-4.24) ; Set value of ‘Average Torque Load Factor Trigger 1’ Signal
•
0x2419 (Ft-4.25) ; Set value of ‘Average Torque Load Factor Trigger 2’ Signal
The outputs of ‘Average Torque Load Factor Trigger 1 and 2 Signals’ should be assigned
because of sequence output signals. See “Allocation Method for Sequence Output Signal” in
the page 3-18.
•
</RMS-CTL1> ; Set ‘Average Torque Load Factor Trigger 1’ Signal
•
</RMS-CTL2> ; Set ‘Average Torque Load Factor Trigger 2’ Signal
Содержание OEMax CSD7
Страница 1: ...CSD7 Servo Drive User Manual Catalog Number s CSD7_ BN F 1 EtherCAT Network type ...
Страница 4: ......
Страница 12: ...viii CSD7 Servo Drive EtherCAT SAFETY FUNCTION CONNECTOR B 6 ...
Страница 23: ...Preface P 11 CSD7 Servo Drive EtherCAT ...
Страница 24: ......
Страница 33: ...Installation 2 5 CSD7 Servo Drive EtherCAT 100W 200W 400W 800W 1KW 1 5KW ...
Страница 38: ......
Страница 76: ......
Страница 94: ......
Страница 114: ......
Страница 126: ......
Страница 314: ......
Страница 320: ...A 6 Specification and Exterior Dimensions CSD7 Servo Drive EtherCAT FigureA 5 400W FigureA 6 800W 1 5KW ...
Страница 327: ...able and Connector Specification B 5 CSD7 Servo Drive EtherCAT ...
Страница 330: ......
Страница 331: ...Publication CSD7 UM001A Network EN October 2015 ...
Страница 332: ...Copyright 2015 RS Automation Co Ltd All rights reserved ...