8-6 Tuning by Gain Setting
CSD7 Servo Drive (EtherCAT)
Setting Parameter
Set the Inertia Ratio to the following parameter.
0x2004
Inertia Ratio
CSP
Setting Range
Size (Data Type)
Unit
Access
PDO Map
Attribute
Init Value
Ft-no
0.00
~60.00
2 byte(UINT)
[
배
]
RW
-
Always
1.00
Ft-0.04
Ft-0.04
Inertia Ratio
RSWare : Drive - Motor - Inertia Ratio
Description
Inertia Ratio = Load Inertia /Motor Rotor Inertia
If you know the inertia ratio, you can set the value directly, but
usually it is measured automatically through offline auto tuning.
(See “Off-line Auto Tuning (0x3001, run-01)” on page 9-36.)
If the inertia ratio is changed by auto tuning or manually, the
proper system gain (Ft-1.01) is set, and the 5 basic gains
0x2102(Ft-1.02), 0x2103(Ft-1.03), 0x2107(Ft-1.07), 0x2202(Ft-2.02)
and 0x2402(Ft-4.02) are also changed automatically accordingly.
Based on the motor type and the rated output, the maximum
allowable inertia ratio is as below. When the allowable inertia ratio
exceeds the maximum, you cannot expect a fast response.
Motor
Capacity
Maximum Allowable Inertia Ratio
CSMT/R
100W or less
30 times
Less than 1kW
20 times
1kW
10 times
Содержание OEMax CSD7
Страница 1: ...CSD7 Servo Drive User Manual Catalog Number s CSD7_ BN F 1 EtherCAT Network type ...
Страница 4: ......
Страница 12: ...viii CSD7 Servo Drive EtherCAT SAFETY FUNCTION CONNECTOR B 6 ...
Страница 23: ...Preface P 11 CSD7 Servo Drive EtherCAT ...
Страница 24: ......
Страница 33: ...Installation 2 5 CSD7 Servo Drive EtherCAT 100W 200W 400W 800W 1KW 1 5KW ...
Страница 38: ......
Страница 76: ......
Страница 94: ......
Страница 114: ......
Страница 126: ......
Страница 314: ......
Страница 320: ...A 6 Specification and Exterior Dimensions CSD7 Servo Drive EtherCAT FigureA 5 400W FigureA 6 800W 1 5KW ...
Страница 327: ...able and Connector Specification B 5 CSD7 Servo Drive EtherCAT ...
Страница 330: ......
Страница 331: ...Publication CSD7 UM001A Network EN October 2015 ...
Страница 332: ...Copyright 2015 RS Automation Co Ltd All rights reserved ...