Application
9-5
CSD7 Servo Drive (EtherCAT)
The DB cannot be used while stopping the motor with normal torque
control. The normal torque control is done in servo-ON, but the DB is
only operated in servo-OFF
Dynamic Brake Stop
Dynamic brake stop means that the motor is stopped by built-in dynamic brake circuit.
Free Run Stop
Free run stop means that the motor is stopped by the mechanical friction of load only.
Dynamic Brake Stop Method
It set the DB (Dynamic Brake) stop method on the below parameter.
0x2002
Selection of Basic Mode
CSP
Sub-Index 1
DB stop method
Setting Range
Size (Data Type)
Unit
Access
PDO Map
Attribute
Init Value
Ft-no
0~3
1 byte(USINT)
-
RW
-
Servo Off
0
Ft-0.02[D0]
[Ft-0.02][D0]
Selection of DB Stop Method
Description
0: The motor is stopped by DB, and DB keep holding the motor even after the motor stop.
1: The motor is stopped by DB, and DB is released after the motor stop.
2: The DB function is not used, but the motor is stopped by free running.
3: The motor is stopped by free running, and DB keep holding the motor after the motor stop.
드라이브
서보
모터
다이나믹
브레이크
i
CAUTION
Содержание OEMax CSD7
Страница 1: ...CSD7 Servo Drive User Manual Catalog Number s CSD7_ BN F 1 EtherCAT Network type ...
Страница 4: ......
Страница 12: ...viii CSD7 Servo Drive EtherCAT SAFETY FUNCTION CONNECTOR B 6 ...
Страница 23: ...Preface P 11 CSD7 Servo Drive EtherCAT ...
Страница 24: ......
Страница 33: ...Installation 2 5 CSD7 Servo Drive EtherCAT 100W 200W 400W 800W 1KW 1 5KW ...
Страница 38: ......
Страница 76: ......
Страница 94: ......
Страница 114: ......
Страница 126: ......
Страница 314: ......
Страница 320: ...A 6 Specification and Exterior Dimensions CSD7 Servo Drive EtherCAT FigureA 5 400W FigureA 6 800W 1 5KW ...
Страница 327: ...able and Connector Specification B 5 CSD7 Servo Drive EtherCAT ...
Страница 330: ......
Страница 331: ...Publication CSD7 UM001A Network EN October 2015 ...
Страница 332: ...Copyright 2015 RS Automation Co Ltd All rights reserved ...