Rockwell Automation Publication 1783-UM007F-EN-P - September 2016
Chapter 5
Install Stratix 5700 Switches
To attach the switch to a DIN rail, follow these steps.
1. Position the rear panel of the switch directly in front of the DIN rail.
Make sure that the DIN rail fits in the space between the two hooks near
the top of the switch and the spring-loaded latch near the bottom.
2. Hold the bottom of the switch away from the DIN rail, and place the
two hooks on the back of the switch over the top of the DIN rail.
3. Push the switch toward the DIN rail to cause the spring loaded latch at
the bottom rear of the switch to move down and snap into place.
ATTENTION:
The console ports are intended for temporary local
programming purposes only and not intended for permanent connection.
The console port cables are not to exceed 3.0 m (9.84 ft) and must not contain
hubs.
ATTENTION:
Under certain conditions, viewing the optical port may expose
the eye to hazard. When viewed under some conditions, the optical port may
expose the eye beyond the maximum permissible exposure
recommendations.
ATTENTION:
Class 1 laser product. Laser radiation is present when the
system is open and interlocks bypassed. Only trained and qualified personnel
should be allowed to install, replace, or service this equipment.
ATTENTION:
This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper grounding.
The use of other DIN rail materials (for example, aluminum or plastic) that
can corrode, oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface approximately
every 200 mm (7.8 in.) and use end-anchors appropriately.
IMPORTANT
The switch must be mounted in an upright orientation, as shown in these
instructions. Alternative mounting orientations are not supported.
32285-M
Содержание ArmorStratix 5700 series
Страница 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Страница 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Страница 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Страница 156: ...156 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 5 Install Stratix 5700 Switches Notes...
Страница 370: ...370 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 7 Configure Switch Features...
Страница 407: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 407 Monitor the Switch Chapter 8...
Страница 409: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 409 Monitor the Switch Chapter 8...
Страница 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Страница 494: ...494 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix B Port Assignments for CIP Data Notes...
Страница 540: ...540 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix D Cables and Connectors Notes...
Страница 547: ......