When determining where to place the switch, observe these guidelines:
• Operating environment is within the range specified in the technical
specifications. See the Stratix Ethernet Managed Switches Technical
Data, publication
• Clearance to front and rear panels meets these conditions:
– Front-panel status indicators can be easily read.
– Access to ports is sufficient for unrestricted cabling.
– Front-panel direct current (DC) power and relay connector is within
reach of the connection to the DC power source.
• Airflow around the switch and through the vents is unrestricted.
To prevent the switch from overheating, observe these minimum
clearances:
– Top and bottom: 105 mm (4.13 in.)
– Left and right: 90 mm (3.54 in.)
– Front: 65 mm (2.56 in.)
• Temperature surrounding the unit does not exceed 60 °C (140 °F).
• Cabling is away from sources of electrical noise, such as radios, power
lines, and fluorescent lighting fixtures.
• Switch is grounded to a bare metal surface, such as a ground bus or a
grounded DIN rail.
Follow these steps to install the switch.
1. (Optional) Attach expansion modules.
2. Mount the switch on one of the following:
• DIN rail
• Wall or panel
3. (Optional) Install an SFP module.
4. Ground the switch.
5. Wire the DC power source for the switch.
6. (Optional) Wire the DC power source for the PoE expansion module.
7. Attach the power and alarm connector.
IMPORTANT
When the switch is installed in an industrial enclosure, the
temperature within the enclosure is greater than normal room
temperature outside the enclosure.
The temperature inside the enclosure cannot exceed 60 °C (140 °F),
the maximum ambient enclosure temperature of the switch.
Содержание ArmorStratix 5700 series
Страница 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Страница 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Страница 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Страница 156: ...156 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 5 Install Stratix 5700 Switches Notes...
Страница 370: ...370 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 7 Configure Switch Features...
Страница 407: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 407 Monitor the Switch Chapter 8...
Страница 409: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 409 Monitor the Switch Chapter 8...
Страница 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Страница 494: ...494 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix B Port Assignments for CIP Data Notes...
Страница 540: ...540 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix D Cables and Connectors Notes...
Страница 547: ......