Configure Switch Features
Chapter 7
View Time Sync Information in the Logix Designer Application
In the navigation pane, click Time Sync Information.
The Time Sync Information view shows current information about the real-
time clocks in the network. The CIP Time Synchronization protocol provides
a standard mechanism to synchronize clocks across a network of distributed
devices.
The CIP Sync Time Synchronization feature supports both Boundary and
End-to-End Transparent mode. End to End Transparent mode synchronizes all
switch ports with the grandmaster clock using the IEEE 1588 V 2 End to End
Transparent clock mechanism, and is the preferred mode.
Delay Request Interval
Type the recommended to connected devices to send delay request messages when the switch port is in the master state.
Valid values:
• -1—half second
• 0—1 second
• 1—2 seconds
• 2—4 seconds
• 3—8 seconds
• 4—16 seconds
• 5—32 seconds
• 6—64 seconds
Default: 5 (32 seconds)
Announce Timeout
Type the number of announce intervals, specified as the logarithmic mean in seconds, that must pass without receipt of an announce message
from the parent or grand master clock before the switch selects a new parent or grand master clock.
Valid values: 2…10
Default: 3 (8 seconds)
Announce Interval
Type the time interval, specified as the logarithmic mean in seconds, for sending announce messages.
Valid values:
• 0—1 second
• 1—2 seconds
• 2— 4 seconds
• 3— 8 seconds
• 4—16 seconds
Default: 1 (2 seconds)
Sync Interval
Type the time interval, specified as the logarithmic mean in seconds, for sending synchronization messages.
Valid values:
• -1—half second
• 0—1 second
• 1— 2 seconds
Default: 0 (1 second)
Sync Fault Limit
Type the maximum clock offset before PTP attempts to reacquire synchronization.
Valid values: 50…500000000 nanoseconds
Default: 50000 nanoseconds
IMPORTANT:
We recommend against setting the sync limit below the default (50000 nanoseconds). Use values below 50000 nanoseconds only in
networks with a very high-precision grandmaster clock. These networks have a critical need to keep very sensitive devices synchronized.
Table 39 - NTP-PTP Mode Fields (Continued)
Field
Description
Содержание ArmorStratix 5700 series
Страница 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Страница 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Страница 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Страница 156: ...156 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 5 Install Stratix 5700 Switches Notes...
Страница 370: ...370 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 7 Configure Switch Features...
Страница 407: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 407 Monitor the Switch Chapter 8...
Страница 409: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 409 Monitor the Switch Chapter 8...
Страница 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Страница 494: ...494 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix B Port Assignments for CIP Data Notes...
Страница 540: ...540 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix D Cables and Connectors Notes...
Страница 547: ......