Rockwell Automation Publication 1783-UM007F-EN-P - September 2016
383
Monitor the Switch
Chapter 8
Stratix 8000/8300 Front Panel
Table 101 - Stratix 8000/8300 System Status Indicators
Indicator
Status
Description
EIP Mod
The EIP Mod status indicator shows the status of the switch.
Off
Power to the switch is off or is not properly connected.
Solid green
The switch is operating properly.
Flashing green
The switch is not configured. For example, the switch does not have an IP address configured.
Flashing red
The switch has detected a recoverable system fault. Use the system log to see more details about the problem. See
Solid red
The switch has detected a nonrecoverable system. Use the system log to see more details about the problem. See
Flashing green and red
The switch is running its power-on self-test (POST).
EIP Net
The EIP Net status indicator shows the network status of the switch.
Off
Power to the switch is off or is not properly connected.
Solid green
The switch has an established CIP connection to one or more attached devices.
Flashing green
The switch has an IP address but the switch does not have an established connection to one or more attached devices.
Flashing red
One or more connections to attached devices have timed out.
Solid red
The switch has detected that its IP address is already in use by another device in the network.
Flashing green and red
The switch is running its power-on self-test (POST).
Setup
The configuration mode in which the switch is operating.
Off
The switch is configured as a managed switch or the switch is operating as an unmanaged switch.
Flashing green
Switch is in the initial Setup mode or is in the Direct Managed mode, or the initial setup is incomplete.
Pwr A and Pwr B The Pwr status indicators show the DC power status.
Off
Power to the switch is off or is not properly connected.
Solid green
Power is present.
Solid red
Power to the switch is not present and the power alarm is on.
Содержание ArmorStratix 5700 series
Страница 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Страница 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Страница 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Страница 156: ...156 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 5 Install Stratix 5700 Switches Notes...
Страница 370: ...370 Rockwell Automation Publication 1783 UM007F EN P September 2016 Chapter 7 Configure Switch Features...
Страница 407: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 407 Monitor the Switch Chapter 8...
Страница 409: ...Rockwell Automation Publication 1783 UM007F EN P September 2016 409 Monitor the Switch Chapter 8...
Страница 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Страница 494: ...494 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix B Port Assignments for CIP Data Notes...
Страница 540: ...540 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix D Cables and Connectors Notes...
Страница 547: ......