6. RKC COMMUNICATION
IMS01J02-E4
87
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
AI input range number
[H-AI-A/B]
VK
6 R/W
C 0: 0 to 10 mV DC
1:
10 to
10 mV DC
2: 0 to 100 mV DC
3:
100 to
100 mV DC
4: 0 to 1 V DC
5:
1 to
1 V DC
6: 0 to 5 V DC
7: 1 to 5 V DC
8:
5 to
5 V DC
9: 0 to 10 V DC
10:
10 to
10 V DC
11: 0 to 20 mA DC
12: 4 to 20 mA DC
Voltage (low) input group:
0 to 8
Voltage (high) input group:
9 to 10
Current input group: 11 to 12
An input type change may
only be made within the input
groups.
If the input range number is
changed, all of the settings
corresponding to the channels
in the relevant module return
to the default values.
The factory
set value
varies
depending
on the
specifications
when
ordering.
AI display scale high
[H-AI-A/B]
JS
6
R/W
C
Span 10000 or less *
(Within
9999 to
10000)
100.0
AI display scale low
[H-AI-A/B]
JV
6
R/W
C
Span 10000 or less *
(Within
9999 to
10000)
0.0
AI alarm 1 differential
gap
[H-AI-A/B]
HC
6
R/W
U
0.00 to 10.00 % of span
0.10
AI alarm 2 differential
gap
[H-AI-A/B]
HF
6
R/W
U
0.00 to 10.00 % of span
0.10
* The position of the decimal point differs depending on AI decimal point position (Identifier: JU)
setting.