7. MODBUS
IMS01J02-E4
151
Continued from the previous page.
(4)
Correspondence module:
The function module name that data becomes valid is written.
Data of following address with H-TIO-
/H-CIO-A module is different from H-SIO-A
module. Data is discriminated by channel number (module number).
Address For
H-TIO-
/H-CIO-A module
For H-SIO-A module
0000H ( 0) to 0013H ( 19)
Temperature measured value (PV)
CH1 to CH20
Motor speed measured value
CH1 to CH20
00C8H ( 200) to 00DBH ( 219)
Temperature set value (SV)
CH1 to CH20
Motor speed set value
CH1 to CH20
0744H (1860) to 074DH (1869)
Cascade DI function selection
Module 1 to Module 10
DI process selection
Module 1 to Module 10
For the channel number, see the
8.2.9 Assignment of channels (P. 183)
.
7.4.2 Data map list
(1) Read only data
Address CH
Name
Address CH
Name
0000H ( 0) CH1
Temperature measured value
(PV)
0078H ( 120)
Temperature rise completion
status
(for each control unit)
H-TIO-
, H-CIO-A
H-TIO-
, H-CIO-A
Motor speed measured value
0013H ( 19) CH20
H-SIO-A
0014H ( 20) CH1 Heat-side manipulated output
value
H-TIO-
, H-CIO-A, H-SIO-A
0079H ( 121)
Error code
(for each control unit)
H-PCP-J
0027H ( 39) CH20
0028H ( 40) CH1 Cool-side manipulated output
value
H-TIO-
, H-CIO-A, H-SIO-A
007AH ( 122)
Overall alarm status
(for each control unit)
H-PCP-J
003BH ( 59) CH20
003CH ( 60) CH1 Current transformer input
measured value 1
H-TIO-A/C/D
007BH ( 123)
Do not use this address range
004FH ( 79) CH20
008BH ( 139)
0050H ( 80) CH1 Current transformer input
measured value 2
H-CT-A
008CH ( 140)
CH1
Set value monitor
H-TIO-
, H-CIO-A, H-SIO-A
0063H ( 99) CH20
009FH ( 159)
CH20
0064H ( 100) CH1
Status
H-TIO-
, H-CIO-A, H-SIO-A
00A0H ( 160)
CH21 Current transformer input
measured value 2
H-CT-A
0077H ( 119) CH20
00C7H ( 199)
CH60