7. MODBUS
IMS01J02-E4
122
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Comprehensive alarm
status
[H-PCP-J]
RO U
The respective channel status is assigned to
each bit in the holding register.
Bit 0: Logical
OR
of alarm 1 status in all
channels
Bit 1: Logical
OR
of alarm 2 status in all
channels
Bit 2: Logical
OR
of burnout alarm status
in all channels
Bit 3: Logical
OR
of heater break alarm
status in all channels
Bit 4: Temperature rise completion status
Bit 5: Logical
OR
of AI alarm 1 status in
all channels
Bit 6: Logical
OR
of AI alarm 2 status in
all channels
Bit 7: Logical
OR
of control loop break
alarm status in all channels
Bit 8: Logical
OR
of TI alarm 1 status in all
channels
Bit 9: Logical
OR
of TI alarm 2 status in all
channels
Bit 10: Logical
OR
of TI burnout alarm
status in all channels
Bit 11 to 15: Unused
Bit data 0: OFF 1: ON
[Decimal number: 0 to 2047]
Set value monitor
[H-TIO-
, H-CIO-A,
H-SIO-A]
RO C
TC/RTD input:
Within input range
Voltage/Current input, H-SIO-A:
Within display scale range
Temperature set value
(SV)
[H-TIO-
, H-CIO-A]
R/W C
TC/RTD input:
Within input range (Within setting limiter)
Voltage/Current input:
Within display scale range
(Within setting limiter)
0 *
Motor speed set value
[H-SIO-A]
R/W C
Within display scale range
(Within setting limiter)
0 *
Item stored in the memory area.
* The position of the decimal point differs depending on the input range.
Continued on the next page.