7. MODBUS
IMS01J02-E4
145
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
TI alarm 1 differential gap
[H-TI-A/B/C]
R/W U 0.00 to 10.00 % of span
0.10
TI alarm 2 differential gap
[H-TI-A/B/C]
R/W U
TI alarm 1 type
selection
[H-TI-A/B/C]
R/W
U
0: Process high alarm
1: Process low alarm
2 to 6: No alarm function
The factory
set value
varies
depending
on the
specifications
when
ordering.
TI alarm 2 type
selection
[H-TI-A/B/C]
R/W
U
TI alarm 1 hold action
[H-TI-A/B/C]
R/W U 0: Not provided
1: Provided
The factory
set value
varies
depending
on the
specifications
when
ordering.
TI alarm 2 hold action
[H-TI-A/B/C]
R/W U
TI alarm 1 interlock
[H-TI-A/B/C]
R/W U 0: Not provided
1: Provided
0
TI alarm 2 interlock
[H-TI-A/B/C]
R/W
U
TI alarm 1 action at input
error
[H-TI-A/B/C]
R/W
U
0: Normal alarm action
1: Forced alarm ON when temperature
measured value exceeds abnormal input
trigger input.
0
TI alarm 2 action at input
error
[H-TI-A/B/C]
R/W
U
Number of TI alarm delay
times
[H-TI-A/B/C]
R/W
U
0 to 255 times
0
Continued on the next page.