5. SETTINGS BEFORE OPERATION
IMS01J02-E4
49
5.3 Start-up Procedures
Check prior to power on
Check the following items before turning on the power to the control unit.
Operation environments conform to
3.1
Mounting Cautions (P. 20)
.
Wiring and connections conform to
4. WIRING
(P. 25)
.
Power supply voltage conforms to
2.
SPECIFICATIONS
(P. 14)
.
Check after power on
Check that the RUN lamps on the H-PCP-J and function modules are flashing.
Operation after power on
Action after power on differs depending on control RUN/STOP holding (Identifier: X1) setting.
Control RUN/STOP
holding
(Identifier X1)
Status after power-ON
Operation mode
Control RUN/STOP
0: Not hold
Same as mode before the power
failure
“0: Control STOP”
Stopped until “1: Control RUN”
is instructed from the PLC or host
computer.
1: Hold
Same as mode before the power
failure
Same as status before the power
failure
Control before power failure is
maintained even if no PLC or
host computer is connected.
2: Start-up from control run
status
“1: Monitor” mode
However if the operation mode is
set to “0: Unused,” “0: Unused”
remains unchanged.
“1: Control RUN”
However, no control is performed
until the operation mode is set to
“3: Normal (perform control).”
For the control RUN/STOP holding (Identifier: X1), see the
6.3 Initial Settings (P. 77)
.