8.2.3 Output scale
This function scales the output range between
9999 to
10000.
H-SIO-A output scale high:
Sets the value equivalent to display scale of control output high limit.
Setting rage: H-SIO-A output scale low to 10000
H-SIO-A output scale low:
Sets the value equivalent to display scale of control output low limit.
Setting
rage:
9999 to H-SIO-A output scale high
Example: Output scale setting when the control output value is 9 V DC at maximum motor speed of
1000 mm/min.
Control output:
Voltage output 0 to 10 V DC
Display scale high: 1000
Display scale low: 0
Set 1111 to output scale high, and set 0 to output scale low.
In order to limit the maximum output voltage to 9 V DC, the control output is limited up to
90 % by setting the high limit of the output limiter to 90.0 %.
8.2.4 Output limiter
This function limits the output range of the control output.
Output limiter high:
Sets the high limit value when control output is limited.
Setting rage: Output limiter low to 105.0 %
Output limiter low:
Sets the low limit value when control output is limited.
Setting
rage:
5.0 % to Output limiter high
= 1111
Display scale high (1000)
Control output high limit
(10 V DC)
Output scale high =
Control output value at maximum
motor speed (9 V DC)
1111 (10 V DC)
←
Output scale high
1000 (9 V DC)
0 (0 V DC)
←
Output scale low
1111 mm/min
1000 mm/min
0 m/min