7. MODBUS
IMS01J02-E4
134
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Temperature rise
completion hold
function
[H-PCP-J]
R/W
U
0: Not hold
1: Hold
1
Interval time setting
COM.PORT1/
COM.PORT2
[H-PCP-J]
R/W
U
0 to 100 ms
1
Interval time setting
COM.PORT3
[H-PCP-J]
R/W
U
0 to 100 ms
1
PLC scanning time
setting *
[H-PCP-J]
R/W
U
0 to 3000 ms
10
Power supply frequency
selection
[H-PCP-J]
R/W
U
0: 50 Hz
1: 60 Hz
0
H-PCP-J module
DO de-energized
selection
[H-PCP-J]
R/W U
The respective channel status is assigned to
each bit in the holding register.
Bit 0: DO1
Bit 1: DO2
Bit 2: DO3
Bit 3: DO4
Bit 4: DO5
Bit 5: DO6
Bit 6: DO7
Bit 7: DO8
Bit 8 to 15: Unused
Bit data 0: Energized 1: De-energized
[Decimal number: 0 to 255]
0
Number of HBA trigger
points
[H-CT-A]
R/W
U
0 to 255 times
5
* Set the PLC scanning time (time of waiting for a response from the PLC) so as to adapt to the
environment used.
Setting example:
Set PLC scanning time to any value more than twice as long as the
maximum scanning time of PLC.
If PLC scanning time is extremely short (When at a factory set value of 10 ms as an example), the
SR Mini HG SYSTEM may detect the time-out not conducting normal communication processing.
The maximum scanning time of PLC differs depending on the CPU processing speed, I/O unit
configuration and the user program capacity of the PLC.
Continued on the next page.