7. MODBUS
IMS01J02-E4
121
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Status
[H-TIO-
, H-CIO-A,
H-SIO-A]
RO C
The respective channel status is assigned to
each bit in the holding register.
Bit 0: Alarm 1 status
Bit 1: Alarm 2 status
Bit 2: Burnout status
Bit 3: Heater break alarm status
(
OR
operation of the H-TIO-
module and H-CT-A module.)
Bit 4: Control loop break alarm (LBA)
status
Bit 5: Temperature rise completion status
Bit 6: Heat-side manipulated output status
Bit 7 to 15: Unused
Bit data 0: OFF 1: ON
[Decimal number: 0 to 127]
For H-SIO-A module, only alarm 1 status
(Bit 0), alarm 2 status (Bit 1), heat-side
manipulated output status (Bit 6) are
effective.
Temperature rise
completion status
[H-TIO-
, H-CIO-A]
RO
U
0: Rise not complete
1: Rise completed
Error code
[H-PCP-J]
RO U
0: Operations normal
1: Backup data check error
2: RAM read/write error
3: System structure error
4: Internal communications error
5: A/D converter error
6: Adjustment data error
Continued on the next page.