7. MODBUS
IMS01J02-E4
120
7.3.3 Communication data list
If you add or delete a function module, or change the arrangement of the modules, or replace a
module with a different model, be sure to perform “Module initialization (Register addresses:
02BFH)” (P. 127, 153) before setting the data.
“Module initialization” stores the new module configuration in the H
-PCP-J
module.
If data is set before “Module initialization” is performed, the H
-PCP-J
module will set the
previously stored initial data of the old modules in the new modules, which may cause
malfunction.
Name
:
Item stored in the memory area.
[ ]: The function module name that data becomes valid is written.
Attributes
RO: Read only
Slave (SR Mini HG SYSTEM)
→
Master
R/W: Read and Write
Slave (SR Mini HG SYSTEM)
Master
WO: Write only
Slave (SR Mini HG SYSTEM)
Master
Structure
C: Data for each channel
L: Data for each event input logic circuit
M: Data for each module
U: Data for each unit address
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Temperature measured
value (PV)
[H-TIO-
, H-CIO-A]
RO C
TC/RTD input:
Within input range
Voltage/Current input:
Within display scale range
Motor speed measured
value
[H-SIO-A]
RO C
Within display scale range
Heat-side manipulated
output value
[H-TIO-
, H-CIO-A,
H-SIO-A]
RO C
5.0 to
105.0 %
Cool-side manipulated
output value
[H-TIO-
, H-CIO-A]
RO C
5.0 to
105.0 %
Current transformer
input measured value 1
[H-TIO-A/C/D]
RO
C
0.0 to 100.0 A or 0.0 to 30.0 A
Current transformer (CT) input measured
value of the H-TIO-A/C/D module.
Current transformer
input measured value 2
[H-CT-A]
RO C
0.0 to 100.0 A or 0.0 to 30.0 A
Current transformer (CT) input measured
value of the H-CT-A module.
Continued on the next page.
CAUTIONS