7. MODBUS
IMS01J02-E4
131
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Decimal point position
[H-TIO-H/J, H-CIO-A,
H-SIO-A]
R/W C 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
H-TIO-H/J,
H-CIO-A: 1
H-SIO-A: 0
Input range number
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C H-TIO-A/B/C/D/K/P:
0 to 63
H-TIO-E/F/G/R, H-CIO-A: 0 to 120
H-TIO-H/J, H-CIO-A:
0 to 12
H-SIO-A: 0
(Fixed)
If the input range number is changed, all of
the settings corresponding to the channels in
the relevant module return to the default
values.
See
Input range table (P. 103)
The factory
set value
varies
depending
on the
specifications
when
ordering.
Setting limiter high
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C TC/RTD input:
Setting limiter low to Input range (high)
Input range
(high)
C
Voltage/Current input, H-SIO-A:
Setting limiter low to Display scale high
Display
scale high
Setting limiter low
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C TC/RTD input:
Input range (low) to Setting limiter high
Input range
(low)
C
Voltage/Current input, H-SIO-A:
Display scale low to Setting limiter high
Display
scale low
Input error
determination point
(high)
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C TC/RTD
input:
Within input range
Input range
(high)
C
Voltage/Current input, H-SIO-A:
Within display scale range
Display
scale high
Input error
determination point
(low)
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C TC/RTD
input:
Within input range
Input range
(low)
C
Voltage/Current input, H-SIO-A:
Within display scale range
Display
scale low
Action at input error
(high)
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C 0:
Normal
control
1: Manipulated output value at input error
0
*
Action at input error
(low)
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C 0:
Normal
control
1: Manipulated output value at input error
0
* Heat control (H-TIO-
/H-CIO-A): 0
Heat/Cool control (H-TIO-
/H-CIO-A): 1
Position proportioning control (H-TIO-K): 0
Speed control (H-SIO-A): 0
Continued on the next page.